The wire is intended for use in electrical installations and devices, as well as antennas.
INSTALLATION AND OPERATION INSTRUCTIONS
Climatic version of wires: B, placement category 2 according to GOST 15150. Operating temperature range:
from -60 ° С to + 55 ° С.
The wires are resistant to atmospheric pressure: from 133 · 10 -4 kPa to 294 kPa.
The wires are resistant to dew, hoarfrost, rain, sea fog, solar radiation, sand, and mold.
Copper wires twisted into strands, which in turn are twisted into a wire with a cross section from 1.5 to 300 mm 2 . Nearby located strands of strand are twisted in different directions. The outer strand of strands has a left twist direction.
TU 16-705.466-87
| Nominal section of a wire, mm2 | Breaking strength, N, not less |
| 1.5 | 560 |
| 2.5 | 960 |
| 4.0 | 1510 |
| 6.0 | 2100 |
| 10.0 | 3920 |
| 16.0 | 6130 |
| Nominal section of a wire, mm2 | Nominal wire diameter, mm | Number of wires | Design diameter mm | Mass 1 km of wire, kg | Maximum current load, A |
| 1.5 | 0.32 | 19 | 1,60 | 14.0 | 10 |
| 1.5 * | 0.20 | 49 | 1.80 | 14.0 | 10 |
| 2.5 | 0.26 | 49 | 2,34 | 24.0 | 16 |
| 4.0 | 0.32 | 49 | 2.88 | 36.0 | 25 |
| 6.0 | 0.38 | 49 | 3.42 | 50.8 | 37 |
| 10.0 | 0.52 | 49 | 4.68 | 95.0 | 60 |
| 10.0 * | 0.30 | 140 | 4.77 | 91.0 | 60 |
| 16.0 | 0.64 | 49 | 5.76 | 144 | 92 |
| 16.0 * | 0.30 | 224 | 6.03 | 145 | 92 |
| 25.0 | 0.58 | 98 | 7.67 | 237 | 137 |
| 35.0 | 0.58 | 133 | 8.70 | 322 | 173 |
| 50.0 | 0.68 | 133 | 10,20 | 442 | 219 |
| 70.0 | 0.68 | 189 | 12.55 | 629 | 267 |
| 95.0 | 0.68 | 259 | 14.28 | 861 | 319 |
| 120.0 | 0.77 | 259 | 16.17 | 1104 | 395 |
| 150.0 | 0.85 | 259 | 17.85 | 1346 | 465 |
| 185.0 | 0.80 | 361 | 20.00 | 1662 | 538 |
| 240.0 | 0.85 | 427 | 22.95 | 2219 | 684 |