The cable is intended for installation in alarm systems, signaling, sound warning and other similar systems, as well as for data processing systems and for transmitting analog or digital data in industrial electronics and control in facilities with increased requirements for fire protection, in particular, in fire alarm systems and automatic fire systems. Halogen-free cables are used where, in the event of a fire, increased safety for people and expensive electronic equipment is required. Supported cable functions - data transmission, supply voltage to equipment that must operate in a fire and during a fire extinguishing (for example, emergency lighting). The cables are fire resistant and their smoke emission is low, the emitted fumes are non-toxic and non-corrosive.
1. Conducting vein: copper single-wire or multi-wire (1 or 2 class, \ according to DSTU EN60228);
2. Insulation - double layer:
- mica tape;
- halogen free compound.
(Insulated conductors are twisted in pairs)
3. Belt insulation: polymer tape;
4. Screen (general, electrostatic) - aluminum-polymer foil and tinned drain wire;
5. Shell: halogen-free compound of red color (other color on request).
TU U 31.3-00217099-021: 2005;
DSTU EN 60228;
DSTU IEC 60502.
| Operating temperature | from -50 ° С to + 50 ° С |
| Minimum cable routing temperature without preheating | -15 ° C |
| Permissible core heating temperature | + 90 ° C |
| Minimum bending radius when laying: | 7.5 cable diameters |
| Minimum service life | 30 years |
| Cable size | Estimated outer diameter of the cable, mm (informative) | Mass of cable, kg / km (informative) |
| KMPvVEng-FRHF (JE-H (St) H BD FE 180 / E30) 1 * 2 * 0.5 | 8.2 | 84 |
| KMPvVEng-FRHF (JE-H (St) H BD FE 180 / E30) 1 * 2 * 1.0 | 10.3 | 124 |
| KMPvVEng-FRHF (JE-H (St) H BD FE 180 / E30) 1 * 2 * 1.5 | 11,2 | 148 |
| KMPvVEng-FRHF (JE-H (St) H BD FE 180 / E30) 2 * 2 * 0.5 | 9.1 | 111 |
| KMPvVEng-FRHF (JE-H (St) H BD FE 180 / E30) 4 * 2 * 0.5 | 15,2 | 231 |
| KMPvVEng-FRHF (JE-H (St) H BD FE 180 / E30) 8 * 2 * 0.5 | 26.1 | 477 |
| KMPvVEng-FRHF (JE-H (St) H BD FE 180 / E30) 10 * 2 * 0.5 | 26.7 | 488 |
| KMPvVEng-FRHF (JE-H (St) H BD FE 180 / E30) 2 * 2 * 0.9 | eleven | 150 |
| KMPvVEng-FRHF (JE-H (St) H BD FE 180 / E30) 4 * 2 * 0.9 | 16.5 | 265 |
| KMPvVEng-FRHF (JE-H (St) H BD FE 180 / E30) 5 * 2 * 0.9 | 18 | 310 |
| KMPvVEng-FRHF (JE-H (St) H BD FE 180 / E30) 15 * 2 * 0.9 | 28.5 | 710 |
| KMPvVEng-FRHF (JE-H (St) H BD FE 180 / E30) 24 * 2 * 0.9 | 35 | 1051 |